2XS(F)2Y-TRIPLEX N2XS(F)2Y -TRIPLEX A2XS(F)2Y-TRIPLEX NA2XS(F)2Y-TRIPLEX
Product Description
2XS(F)2Y-TRIPLEX / N2XS(F)2Y -TRIPLEX A2XS(F)2Y-TRIPLEX / NA2XS(F)2Y-TRIPLEX
Uo/U – 6/10 kV, 12/20 kV, 18/30kV IEC 60502-2 / DIN VDE 0276-620
The three single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements, factory bindled in TRIPLEX, are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20; 18/30 kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer’s substations, small and medium industrial plants.
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
| Construction | According to IEC 60502-2DIN VDE 0276-620 |
| Conductors | Cu and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2 |
| Inner semi-conductive layer | semi-conductive XLPE compound |
| Insulation | XLPE compound |
| Outer semi-conductive layer | semi-conductive XLPE compound |
| Water resisting element | Layer of semi-conductive water absorbing tapes |
| Metal screen | Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm. |
| Water resisting element | -I option – water absorbing insulating tape -II option – water absorbing powder and a layer of plastic tape |
| Sheath | PE compound type ST7 according to IEC 60502 type DMP 2 according to VDE 0276 |
| Color | Black |
| Factory bundled in TRIPLEX | three single-core cables factory bindled in TRIPLEX |
| Conductor resistance at 20°C | According to IEC60228 class 2 and VDE 0295 class 2 |
| Operating temperature | 90°C continuous operation |
| Overload temperature | 130°C /100h per year max./ |
| Short circuit temperature | 250°C /5 s max./ |
| Nominal voltage Uo/U: | 6/10; 12/20; 18/30 kV |
| Highest system voltage Uo/U, no more than | 6/10; 12/20; 18/30 kV 12kV; 24kV; 36kV |
| Test voltage Uo/U AC (≈) – 5 min DC (=) – 15 min | 6/10; 12/20; 18/30kV 21kV; 42kV; 63kV 67kV; 134kV; 201kV |
| Level of partial discharge at 2*Uo Bending radius, min Temperature of laying | max. 5 pC / 2 pC 15x D cable no less than – 20°C |
| Temperature of exploitation Tests | -30 to 50°C according to IEC 60502-2 or DIN VDE 0276-620 |
| Force of strain in laying N max. | Al cores – 30*n*S core Cu cores – 50*n*S core |
| where: Tests – water penetration in the region of metallic screen | N is number of cores and S is cross section of cores in mm IEC 60502-2 annex F |
| Number of conductors and nominal cross section | Thickness of insulation | Thickness of sheath | Nominal cross section of screen | Cable diameter approx. | 2XS(F)2Y-TRIPLEX N2XS(F)2Y- TRIPLEX | A2XS(F)2Y- TRIPLEX NA2XS(F)2Y- TRIP EX | ||||||||||||||||
| Mass of Cu approx. | Mass of cable approx. | Mass of Al approx. | Mass of Cu approx. | Mass of cable approx. | ||||||||||||||||||
| Nxmm2 | mm | mm | mm | min mm | max mm | kg/km | kg/km | kg/km | kg/km | kg/km | ||||||||||||
| 6/10 kV | ||||||||||||||||||||||
| 3x(1x35rm/16) 3x(1x50rm /16) | 3,4 | 2,5 | 16 | 49.7 51.8 | 60.5 62.6 | 1479 1812 | 2718 3129 | 282 | 528 | 2049 2235 | ||||||||||||
| 3,4 | 2,5 | 16 | 381 | 528 | ||||||||||||||||||
| 3x(1x70rm /16) | 3,4 | 2,5 | 16 | 56.2 | 67 | 2379 | 3837 | 549 | 528 | 2538 | ||||||||||||
| 3x(1x95rm /16) | 3,4 | 2,5 | 16 | 58.3 | 69.2 | 3099 | 4692 | 762 | 528 | 2883 | ||||||||||||