NA2XSY Cable
Product Description
Product Description
NA2XSY Cable 6/10 kV 12/20 kV 18/30 kV| XLPE Insulated Single-Core Cable with PVC Outer Sheath
NA2XSY Cable Application
To be laid directly in ground, outdoors, indoors and in cable ducts.
NA2XSY Cable Construction
1…..stranded (RM) aluminium wires
2…..inner layer of semi-conducting material
3…..core insulation of cross-linked polyethylene
4…..outer layer of semi-conducting material
5…..screen of copper wires
6…..outer sheath of polyvinylchloride (PVC), red
NA2XSY Cable Standards
DIN VDE0276-620 HD 620 S1: 1995 DIN EN 60228 class 2 (construction)
0.6/1kV Aerial Bundle Cable ASNZS 3560.1 Specifications
| Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
| 12 / 20 kV | [kV] | 42 / 5 min. | |
| 18 / 30 kV | [kV] | 63 / 5 min. | |
| Temperature range | in motion | – 5°C till +70°C | |
| fixed | -20°C till +70°C | ||
| Operating temperature | short circuit | °C | 250 |
| Short circuit time | max. | [sec] | 5 |
| Bending radius | min. | x diameter | 15 |
| Flammability | standard | EN 60332-1-2 |
| Number of cores and nominal cross section mm² | Aluminium figure kg/km | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
|---|---|---|---|---|---|---|---|
| 6 / 10 kV | |||||||
| 1 x 35 RM/16 | 103 | 182,40 | 23 | 28 | 700 | 145 | 153 |
| 1 x 50 RM/16 | 147 | 182,40 | 24 | 29 | 750 | 171 | 183 |
| 1 x 70 RM/16 | 206 | 182,40 | 26 | 31 | 850 | 208 | 228 |
| 1 x 95 RM/16 | 279 | 182,40 | 27 | 32 | 950 | 248 | 278 |
| 1 x 120 RM/16 | 353 | 182,40 | 29 | 34 | 1.050 | 283 | 321 |
| 1 x 150 RM/25 | 441 | 283,20 | 30 | 35 | 1.300 | 315 | 364 |
| 1 x 185 RM/25 | 544 | 283,20 | 32 | 37 | 1.400 | 357 | 418 |
| 1 x 240 RM/25 | 706 | 283,20 | 34 | 39 | 1.650 | 413 | 494 |
| 1 x 300 RM/25 | 882 | 283,20 | 36 | 40 | 1.850 | 466 | 568 |
| 1 x 400 RM/35 | 1.176 | 393,60 | 40 | 45 | 2.300 | 529 | 660 |
| Number of cores and nominal cross section mm² | Aluminium figure kg/km | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
|---|---|---|---|---|---|---|---|
| 12 / 20 kV | |||||||
| 1 x 50 RM/16 | 147 | 182,40 | 28 | 33 | 950 | 172 | 185 |
| 1 x 70 RM/16 | 206 | 182,40 | 30 | 35 | 1.050 | 210 | 231 |
| 1 x 95 RM/16 | 279 | 182,40 | 31 | 36 | 1.150 | 251 | 280 |
| 1 x 120 RM/16 | 353 | 182,40 | 33 | 38 | 1.300 | 285 | 323 |
| 1 x 150 RM/25 | 441 | 283,20 | 34 | 39 | 1.500 | 319 | 366 |
| 1 x 185 RM/25 | 544 | 283,20 | 36 | 41 | 1.650 | 361 | 420 |
| 1 x 240 RM/25 | 706 | 283,20 | 39 | 44 | 1.850 | 417 | 496 |
| 1 x 300 RM/25 | 882 | 283,20 | 41 | 46 | 2.100 | 471 | 569 |
| 1 x 400 RM/35 | 1.176 | 393,60 | 44 | 49 | 2.550 | 535 | 660 |
| Number of cores and nominal cross section mm² | Aluminium figure kg/km | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg / km | Current carrying capacity ground A* | Current carrying capacity air A* |
|---|---|---|---|---|---|---|---|
| 18 / 30 kV | |||||||
| 1 x 50 RM/16 | 147 | 182,40 | 36 | 41 | 1.190 | 175 | 187 |
| 1 x 70 RM/16 | 206 | 182,40 | 37 | 42 | 1.315 | 214 | 232 |
| 1 x 95 RM/16 | 279 | 182,40 | 39 | 43 | 1.450 | 256 | 281 |
| 1 x 120 RM/16 | 353 | 182,40 | 40 | 45 | 1.580 | 290 | 323 |
| 1 x 150 RM/25 | 441 | 283,20 | 42 | 47 | 1.800 | 324 | 365 |
| 1 x 185 RM/25 | 544 | 283,20 | 44 | 49 | 1.965 | 366 | 418 |
| 1 x 240 RM/25 | 706 | 283,20 | 46 | 51 | 2.230 | 426 | 494 |
| 1 x 300 RM/25 | 882 | 283,20 | 49 | 53 | 2.470 | 479 | 564 |
| 1 x 400 RM/35 | 1.176 | 393,60 | 51 | 56 | 2.920 | 545 | 654 |