返回顶部
品胜与小米充电宝对比 (4)

NA2XS(F)2Y Cable

  • Category: Low & Medium Voltage CableTag: Power Cables 6 - 30 KV PVC and XLPE Insulated

Product Description

Product Description

NA2XS(F)2Y Cable| Single-Core XLPE Insulated Cable with PE Outer Sheath, longitudinally watertight (6/10 kV, 12/20 kV, 18/30 kV)

NA2XS(F)2Y Cable Application

To be laid directly in ground, outdoors, in water, indoors and in cable ducts.

Cable Construction

1…..stranded (RM) aluminium wire

2…..inner layer of semi-conducting material

3…..core insullation of cross-linked polyethylene

4…..outer layer of semi-conducting material

5…..swellable tape

6…..screen of copper wires

7…..waterproofing tape

8…..outer sheath of polyethylene (PE), black

NA2XS(F)2Y Cable Standards

DIN VDE 0276-620
HD 620 S1: 1995
DIN EN 60228 class 2 (construction)

 

 

图片5.png

Cable Construction

1…..stranded (RM) aluminium wire

2…..inner layer of semi-conducting material

3…..core insullation of cross-linked polyethylene

4…..outer layer of semi-conducting material

5…..swellable tape

6…..screen of copper wires

7…..waterproofing tape

8…..outer sheath of polyethylene (PE), black

NA2XS(F)2Y Cable Standards

DIN VDE 0276-620
HD 620 S1: 1995
DIN EN 60228 class 2 (construction)


NA2XS(F)2Y Cable Technical data

Test voltage6 / 10 kV[kV]21 / 5
min.
 12 / 20 kV[kV]42 / 5
min.
 18 / 30 kV[kV]63 / 5
min.
Temperature rangein motion -20°C till +70°C
 fixed -20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15

 

Number of cores and
nominal cross section
mm²
Aluminium
figurekg/km
Copper
figurekg/km
Overall
diameterappr. mm
Overall
diameter
max. value
appr. mm
Weight
appr.
kg / km
Current carrying
capacity
ground
A*
Current carrying
capacity
air
A*
 
6 / 10 kV        
1 x 50 RM/16147182,402429670171183 
1 x 70 RM/16206182,402631770209226 
1 x 95 RM/16279182,402732880248278 
1 x 120 RM/16353182,402934950283321 
1 x 150 RM/25441283,2030351.150315364 
1 x 185 RM/25544283,2032371.250357418 
1 x 240 RM/25706283,2034391.500413494 
1 x 300 RM/25882283,2036411.700466568 
1 x 400 RM/351.176393,6040452.100529660 
1 x 500 RM/351.479393,6043482.450602767 
1 x 630 RM/351.853393,6049543.060**** 

 

Number of cores and
nominal cross section
mm²
Aluminium
figurekg/km
Copper
figurekg/km
Overall
diameterappr. mm
Overall
diameter
max. value
appr. mm
Weight
appr.
kg / km
Current carrying
capacity
ground
A*
Current carrying
capacity
air
A*
12 / 20 kV       
1 x 50 RM/16147182,402833820172185
1 x 70 RM/16206182,403035930210231
1 x 95 RM/16279182,4031361.050251280
1 x 120 RM/16353182,4033381.150285323
1 x 150 RM/25441283,2034391.350319366
1 x 185 RM/25544283,2036411.500361420
1 x 240 RM/25706283,2039441.750417496
1 x 300 RM/25882283,2041462.000471569
1 x 400 RM/351.176393,6044492.350535660
1 x 500 RM/351.470393,6047522.800609766
1 x 630 RM/351.903393,6052573.400****
1 x 800 RM/352.352393,6058634.400****

 

Number of cores and
nominal cross section
mm²
Aluminium
figurekg/km
Copper
figurekg/km
Overall
diameterappr. mm
Overall
diameter
max. value
appr. mm
Weight
appr.
kg / km
Current carrying
capacity
ground
A*
Current carrying
capacity
air
A*
18 / 30 kV       
1 x 50 RM/16147182,4033381.100174187
1 x 70 RM/16206182,4035401.200213232
1 x 95 RM/16279182,4036411.350254282
1 x 120 RM/16353182,4038431.450289325
1 x 150 RM/25441283,2039441.700322367
1 x 185 RM/25544283,2041461.850364421
1 x 240 RM/25706283,2043482.050422496
1 x 300 RM/25882283,2046512.350476568
1 x 400 RM/351.176393,6049542.800541650
1 x 500 RM/351.510393,6050553.091616764
1 x 630 RM/351.853393,6058633.790****
1 x 800 RM/352.352393,6061664.400****