N2XSEY Cable| Three-Core XLPE Insulation Cable with PVC Outer Sheath
N2XSEY Application
To be laid directly in ground, water, outdoors, indoors and in cable ducts e.g. in industrial and switchboard plants.
N2XSEY Construction

1…..stranded bare copper
2…..inner layer of semi-conducting material
3…..core insulation of cross-linked polyethylene
4…..outer layer of semi-conducting material
5…..semi-conducting tape
6…..screen of copper wires
7…..inner covering over laid-up cores
8…..outer sheath of polyvinylchloride (PVC), red
N2XSEY Standards
DIN VDE 0276-620 HD 620 S1: 1996 IEC 60502 DIN EN 60228 class 2 (construction)
N2XSEY Technical data
| Nominal voltage Uo/U | [V] | 6000 / 10000 Volt | |
| Test voltage | [V]AC | 21000 | |
| Temperature range | in motion | – 5°C till +70°C | |
| fixed | -20°C till +70°C | ||
| Operating temperature | short circuit | °C | 250 |
| Short circuit time | max. | [sec] | 5 |
| Bending radius | min. | x diameter | 15 |
| Flammability | standard | EN 60332-1-2 |
| Number of cores and nominal cross section mm² | Copper figure kg/km | Overall diameter appr. mm | Weight appr. kg / km | Current carrying capacity ground A | Current carrying capacity air A |
|---|---|---|---|---|---|
| 3 x 35 RM/16 | 1.209,60 | 49 | 2.600 | 213 | 213 |
| 3 x 50 RM/16 | 1.622,40 | 51 | 2.900 | 220 | 236 |
| 3 x 70 RM/16 | 2.198,40 | 55 | 3.350 | 261 | 265 |
| 3 x 95 RM/16 | 2.994,24 | 58 | 4.200 | 312 | 322 |
| 3 x 120 RM/16 | 3.638,40 | 62 | 5.050 | 355 | 370 |
| 3 x 150 RM/25 | 4.603,20 | 66 | 6.000 | 399 | 420 |
| 3 x 185 RM/25 | 5.611,20 | 69 | 7.200 | 451 | 481 |
| 3 x 240 RM/25 | 7.195,20 | 75 | 9.000 | 523 | 566 |