Product Description
Anti-fraud Copper Aluminum – SEU SER
Service Entrance Cable: Type SE, Style SER and SEU ; Voltage: 600 Volt. ; Conductor: Copper or Aluminum ; Individual Conductors Rated XHHW-2 or THHN/THWN
COPPER SERVICE ENTRANCE CONCENTRIC CABLE American Standard-SE SER SEU TYPE
Service Entrance Cable Application
Type SE, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panel board; however, the cable may be used in all applications where Type SE cable is permitted. SER may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating is 600 volts.
Service Entrance Cable Standard
• ASTM- All applicable standards
• UL Standard 44 for XHHW-2 conductors
• UL Standard 83 for THHN/THWN conductors
• UL Standard 854
• Federal Specification A-A-59544
• National Electrical Code, NFPA 70. 2011 Edition
Service Entrance Cable Construction

Constructed with sunlight resistant Type XHHW-2 conductors or Type THHN/THWN conductors.
Copper conductors are annealed (soft) copper. Cable assembly plus reinforcement tape are jacketed with sunlight resistant
gray polyvinyl chloride (PVC). Available as 1 conductor with a concentric ground, 2 conductor with a round or concentric
ground, or 3 conductor with a bare ground. SE cable is jacketed with gray sunlight resistant polyvinyl chloride (PVC).
ALUMINUM SERVICE ENTRANCE CONCENTRIC CABLE American Standard-SE SER SEU TYPE
Service Entrance Cable Application
Type SE, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panel board; however, the cable may be used in all applications where Type SE cable is permitted. SER may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating is 600 volts.
Service Entrance Cable Standard
• ASTM- B-800 and B-801
• UL Standard 83 for THHN/THWN-2
• UL Standard 44 for XHHW-2
• Federal Specification A-A-59544
• National Electrical Code/NFPA 70, 2011 Edition
• RoHS
Service Entrance Cable Construction


Type SE cable is constructed with AA-8000 series aluminum alloy, compact stranded conductors. The conductors are covered with a sunlight resistant Type XHHW-2 or Type THHN/THWN-2 insulation. A reinforcement tape is wrapped around the conductors for added strength and conformity. A gray sunlight resistant polyvinyl chloride (PVC) outer jacket covers the entire assembly. Style SEU cable has two phase conductors surrounded by a concentric neutral while the SER style has two, three or four phase conductors and a bare neutral.
Style SER Cable’s phase conductors are identified by a colored stripe on the insulation.
3 conductor- Black and Black with Red Stripe
4 conductor- Black, Black with White Stripe, and Black with Red Stripe
5 conductor- Black, Black with White Stripe, Black with Red Stripe and Black with Blue Stripe
Specifications
SER Copper Conductor
0.6/1kV Aerial Bundle Cable ASNZS 3560.1 Specifications
| Size/ Construction (AWG) | Stranding | Nominal O.D. (mils) | Approximate Weight per 1000′ (lbs) | Allowable Ampacities+ | Standard Package | ||||
|---|---|---|---|---|---|---|---|---|---|
| Phase & Neutral Conductors | Equipment Ground Conductor | 60° C | 75° C | 90° C | Dwelling | ||||
| SER Copper TWO CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS “THREE CONDUCTOR”) | |||||||||
| 8-8-8 | 7 | – – | 586 | 231 | 40 | 50 | 55 | – – | B |
| 6-6-6 | 7 | – – | 669 | 338 | 55 | 65 | 75 | – – | B |
| 4-4-4 | 7 | – – | 764 | 498 | 70 | 85 | 95 | 100 | B |
| 3-3-3 | 7 | – – | 829 | 611 | 85 | 100 | 110 | 110 | B |
| 2-2-2 | 7 | – – | 896 | 752 | 95 | 115 | 130 | 125 | B |
| 1-1-1 | 19 | – – | 1021 | 948 | 110 | 130 | 150 | 150 | C |
| 1/0-1/0-1/0 | 19 | – – | 1114 | 1169 | 125 | 150 | 170 | 175 | C |
| 2/0-2/0-2/0 | 19 | – – | 1209 | 1444 | 145 | 175 | 195 | 200 | C |
| 3/0-3/0-3/0 | 19 | – – | 1317 | 1792 | 165 | 200 | 225 | 225 | C |
| 4/0-4/0-4/0 | 19 | – – | 1438 | 2226 | 195 | 230 | 260 | 250 | C |
| SER Copper THREE CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS “FOUR CONDUCTOR”) | |||||||||
| 8-8-8-8 | 7 | 7 | 645 | 286 | 40 | 50 | 55 | – – | B |
| 6-6-6-6 | 7 | 7 | 738 | 424 | 55 | 65 | 75 | – – | B |
| 4-4-4-6 | 7 | 7 | 844 | 585 | 70 | 85 | 95 | 100 | B |
| 3-3-3-5 | 7 | 7 | 910 | 719 | 85 | 100 | 110 | 110 | B |
| 2-2-2-4 | 7 | 7 | 984 | 887 | 95 | 115 | 130 | 125 | B |
| 1-1-1-3 | 19 | 7 | 1132 | 1117 | 110 | 130 | 150 | 150 | C |
| 1/0-1/0-1/0-2 | 19 | 19 | 1235 | 1382 | 125 | 150 | 170 | 175 | C |
| 2/0-2/0-2/0-1 | 19 | 19 | 1342 | 1713 | 145 | 175 | 195 | 200 | C |
| 3/0-3/0-3/0-1/0 | 19 | 19 | 1462 | 2129 | 165 | 200 | 225 | 225 | C |
| 4/0-4/0-4/0-2/0 | 19 | 19 | 1598 | 2650 | 195 | 230 | 260 | 250 | C |
| Conductor | Stranding | Nominal O.D. (mils) | Approximate Weight per 1000′ (lbs) | Allowable Ampacities+ | Standard Package | ||||
|---|---|---|---|---|---|---|---|---|---|
| Size (AWG) | Phase Conductors | Bare Ground | 60° C | 75° C | 90° C | Dwelling | |||
| SEU Copper ONE CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS “TWO CONDUCTOR”) | |||||||||
| 8-8 | 7 | 8 | 400 | 144 | 40 | 50 | 55 | – – | ABC |
| 6-6 | 7 | 12 | 435 | 208 | 55 | 65 | 75 | – – | |
| 4-4 | 7 | 12 | 506 | 315 | 70 | 85 | 95 | – – | C |
| 2-2 | 7 | 15 | 580 | 485 | 95 | 115 | 130 | – – | |
| SEU Copper TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS “THREE CONDUCTOR”) | |||||||||
| 10-10-10 | 1 | 12 | 428 X 283 | 127 | 30 | 30 | 30 | – – | ABC |
| 8-8-8 | 7 | 8 | 587 X 380 | 211 | 40 | 50 | 60 | – – | ABC |
| 6-6-6 | 7 | 12 | 659 X 416 | 308 | 55 | 65 | 75 | – – | BCE |
| 4-4-4 | 7 | 12 | 815 X 506 | 471 | 70 | 85 | 95 | 100 | BCE |
| 3-3-3 | 7 | 12 | 883 X 548 | 583 | 85 | 100 | 110 | 110 | B |
| 2-2-2 | 7 | 15 | 994 X 578 | 718 | 95 | 115 | 130 | 125 | BD |
| 1-1-1 | 19 | 14 | 1093 X 664 | 904 | 110 | 130 | 150 | 150 | B |
| 1/0-1/0-1/0 | 19 | 18 | 1179 X 707 | 1123 | 125 | 150 | 170 | 175 | BC |
| 2/0-2/0-2/0 | 19 | 18 | 1283 X 767 | 1379 | 145 | 175 | 195 | 200 | BC |
| 3/0-3/0-3/0 | 19 | 14 | 1429 X 862 | 1712 | 165 | 200 | 225 | 225 | BD |
| 4/0-4/0-4/0 | 19 | 18 | 1541 X 918 | 2146 | 195 | 230 | 260 | 250 | BC |
| SEU Copper TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMALLY REFERRED TO AS “THREE CONDUCTOR”) (REDUCED NEUTRAL) | |||||||||
| 6-6-8 | 7 | 8 | 659 X 416 | 281 | 55 | 65 | 75 | – – | BC |
| 4-4-6 | 7 | 12 | 790 X 481 | 420 | 70 | 85 | 95 | 100 | BC |
| 3-3-5 | 7 | 15 | 843 X 508 | 515 | 85 | 100 | 110 | 110 | BC |
| 2-2-4 | 7 | 12 | 929 X 563 | 639 | 95 | 115 | 130 | 125 | BC |
| Conductor | Stranding* | Nominal O.D. (mils) | Allowable Ampacities+ | Approx. Net Weight per 1000′ (lbs) | Standard Package | ||||
|---|---|---|---|---|---|---|---|---|---|
| Size/Const. AWG or kcmil | Phase Conductor & Neutral | Equipment Ground Conductor | 60° C | 75° C | 90° C | Dwelling | |||
| SER Aluminum Two Conductor With Bare Ground (Formerly referred to as “EZ-SE”) | |||||||||
| 6-6-6 | 7 | – | 650 | 40 | 50 | 60 | – | 150 | B |
| 4-4-4 | 7 | – | 745 | 55 | 65 | 75 | – | 203 | B |
| 4-4-6 | 7 | – | 745 | 55 | 65 | 75 | – | 203 | B |
| 2-2-2 | 7 | – | 864 | 75 | 90 | 100 | 100 | 290 | B |
| 2-2-4 | 7 | – | 864 | 75 | 90 | 100 | 100 | 290 | B |
| 2/0-2/0-1 | 12 | – | 1140 | 115 | 135 | 150 | 150 | 527 | B |
| 2/0-2/0-2/0 | 12 | – | 1140 | 115 | 135 | 150 | 150 | 527 | B |
| 4/0-4/0-2/0 | 19 | – | 1354 | 150 | 180 | 205 | 200 | 784 | C |
| 4/0-4/0-4/0 | 19 | – | 1354 | 150 | 180 | 205 | 200 | 784 | C |
| SER Aluminum Three Conductor With Bare Ground (Formerly referred to as “Four Conductor”) | |||||||||
| 8-8-8-8 | 1 | 1 | 612 | 30 | 40 | 45 | – | 136 | B |
| 6-6-6-6 | 7 | 7 | 717 | 40 | 50 | 60 | – | 196 | B |
| 4-4-4-6 | 7 | 7 | 823 | 55 | 65 | 75 | – | 252 | B |
| 2-2-2-4 | 7 | 7 | 956 | 75 | 90 | 100 | 100 | 359 | B |
| 1-1-1-3 | 8 | 7 | 1079 | 85 | 100 | 115 | 110 | 449 | C |
| 1/0-1/0-1/0-2 | 10 | 1 | 1168 | 100 | 120 | 135 | 125 | 540 | C |
| 2/0-2/0-2/0-1 | 12 | 1 | 1264 | 115 | 135 | 150 | 150 | 652 | C |
| 3/0-3/0-3/0-1/0 | 16 | 1 | 1371 | 130 | 155 | 175 | 175 | 786 | C |
| 4/0-4/0-4/0-2/0 | 19 | 1 | 1496 | 150 | 180 | 205 | 200 | 960 | C |
| 250-250-250-3/0 | 22 | 1 | 1839 | 170 | 205 | 230 | 225 | 1458 | C |
| SER Aluminum Four Conductor With Bare Ground (Formerly referred to as “Five Conductor”) | |||||||||
| 2-2-2-2-4 | 6 | 7 | 1059 | 75 | 90 | 100 | 100 | 452 | B 5 |
| 2/0-2/0-2/0-2/0-1 | 12 | 1 | 1404 | 115 | 135 | 150 | 150 | 827 | C |
| 4/0-4/0-4/0-4/0-2/0 | 19 | 1 | 1672 | 150 | 180 | 205 | 200 | 1228 | C |
| 50-250-250-250-3/0 | 22 | 1 | 1847 | 170 | 205 | 230 | 225 | C | |
| SEU Aluminum Two Conductor With Bare Concentric Ground (Formerly referred to as “Three Conductor”) | |||||||||
| 6-6-6 | 7 | 8 | 430 X 687 | 40 | 50 | 60 | – | 145 | H |
| 4-4-4 | 7 | 12 | 499 X 800 | 55 | 65 | 75 | – | 198 | I |
| 4-4-6 | 7 | 15 | 474 X 775 | 55 | 65 | 75 | – | 181 | I |
| 2-2-2 | 7 | 14 | 569 X 925 | 75 | 90 | 100 | 100 | 283 | I |
| 2-2-4 | 7 | 18 | 554 X 910 | 75 | 90 | 100 | 100 | 259 | I |
| 2/0-2/0-2/0 | 18 | 18 | 736 X 1221 | 115 | 135 | 150 | 150 | 514 | CJ |
| 2/0-2/0-1 | 18 | 14 | 720 X 1205 | 115 | 135 | 150 | 150 | 468 | CJ |
| 4/0-4/0-4/0 | 18 | 18 | 878 X 1462 | 150 | 180 | 205 | 205 | 765 | CL |
| 4/0-4/0-2/0 | 18 | 18 | 835 X 1419 | 150 | 180 | 205 | 205 | 691 | CL |