MV Aerial Bundled Cables ASNZS 3599.1

  • ABC Cable / Aerial Bundled CableTags: 6.35/11kV & 12.7/22kV ABC, AL/XLPE /CWS/HDPE, AL/XLPE/HDPE;

  • 2KM;

  • Shipping fee and delivery date to be negotiated. Chat with supplier now for more details;

  • Every payment you make is secured with strict SSL encryption and PCI DSS data protection protocols;

  • FOB, CFR, EXW, FAS, DDP;

  • USD, EUR, CAD, AUD, GBP, CNY

Product Description

6.35/11kV & 12.7/22kV ABC –Aerial Bundled Cables to AS/NZS 3599.1

Medium Voltage Aerial Bundled Cables Application

MV Aerial Bundled Cables are mainly used for secondary overhead lines on poles or as feeders to residential premises.

6.35/11kV & 12.7/22kV ABC Cable Construction

6.35/11kV & 12.7/22kV Non Screened MV ABC Cable Aerial Bundled Cables to AS/NZS 3599.1

 

6.35/11kV & 12.7/22kV Screened MV ABC Cable–Aerial Bundled Cables to AS/NZS 3599.1 (AL/XLPE /CWS/HDPE)


6.35/11kV & 12.7/22kV ABC –Aerial Bundled Cables to AS/NZS 3599.1 Specifications

number of cores x nominal cross sectionNominal conductor diameterNominal insulation thicknessNominal insulation screen thicknessNominal sheath thicknessAAAC/1120 support conductor sizeNominal overall diameterWeightContinuous current rating, A
Still air1m/s wind2m/s wind
mm^2mmmmmmmmNo/mmmmkg/kmAAA
6.35/11kV
3×356.93.40.81.27/4.7552.41370110155185
3×508.13.40.81.27/4.7554.61530130185225
3×709.73.40.81.27/4.7557.81790160235280
3×9511.43.40.81.27/4.7561.32100195285345
3×12012.83.40.81.219/3.5067.32540230335405
3×15014.23.40.81.219/3.5070.12840255380460
3×18515.73.40.81.219/3.5073.13190295440530
12.7/22kV
3×356.95.50.81.27/4.7561.01780110155180
3×508.15.50.81.27/4.7563.31970130185220
3×709.75.50.81.27/4.7566.52260160230275
3×9511.45.50.81.27/4.7569.92600195285335
3×12012.85.50.81.219/3.5075.93070225330395
3×15014.25.50.81.219/3.5078.73390255375450
3×18515.75.50.81.219/3.5081.73760290435520

 

Phase ConductorCircular compacted stranded H68 aluminium to BS2627.
Conductor ScreenExtruded semi-conductive layer.
InsulationXLPE.
Insulation ScreenExtruded semi-conductive layer.
Metallic ScreenCopper wire screen.
SeparatorSemi-conductive swellable tape.
Outer SheathHDPE.
Support ConductorGalvanized steel wires.
AssemblyThree XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.

 

number of cores x nominal cross sectionNominal conductor diameterNominal insulation thicknessNominal insulation screen thicknessCopper wire screen strandingNominal sheath thicknessGalvanized steel wire strandingNominal overall diameterWeightContinuous current rating, A
Still air1m/s wind2m/s wind
mm^2mmmmmmNo/mmmmNo/mmmmkg/kmAAA
Light duty screen
3×356.93.40.825/0.851.87/2.0054.1182099140165
3×356.93.40.825/0.851.819/2.0058.12130100145165
3×508.13.40.825/0.851.819/2.0060.42300120170200
3×709.73.40.825/0.851.819/2.0063.62570150215250
3×9511.43.40.825/0.851.819/2.0067.02900180260305
3×12012.83.40.825/0.851.819/2.0069.83190205300355
3×15014.23.40.825/0.851.919/2.0073.03530235340400
3×18515.73.40.825/0.851.919/2.0076.03890265390460
Heavy duty screen
3×356.93.40.840/0.851.87/2.0054.1205099140165
3×356.93.40.840/0.851.819/2.0058.12360100145165
3×508.13.40.823/1.351.819/2.0062.42820120175200
3×709.73.40.832/1.351.819/2.0065.63440150215250
3×9511.43.40.839/1.351.819/2.0069.04030180260305
3×12012.83.40.839/1.351.819/2.0071.84320205300355
3×15014.23.40.839/1.351.919/2.0075.04670230340400
3×18515.73.40.839/1.351.919/2.0078.05020265390460

 

Phase ConductorCircular compacted stranded H68 aluminium to BS2627.
Conductor ScreenExtruded semi-conductive layer.
InsulationXLPE.
Insulation ScreenExtruded semi-conductive layer.
Metallic ScreenCopper wire screen.
SeparatorSemi-conductive swellable tape.
Outer SheathHDPE.
Support ConductorGalvanized steel wires.
AssemblyThree XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.

 

number of cores x nominal cross sectionNominal conductor diameterNominal insulation thicknessNominal insulation screen thicknessCopper wire screen strandingNominal sheath thicknessGalvanized steel wire strandingNominal overall diameterWeightContinuous current rating, A
Still air1m/s wind2m/s wind
mm^2mmmmmmNo/mmmmNo/mmmmkg/kmAAA
Light duty screen
3×356.95.50.825/0.851.87/2.0062.72280100140165
3×356.95.50.825/0.851.819/2.0066.72580105145165
3×508.15.50.825/0.851.819/2.0069.02780125170200
3×709.75.50.825/0.851.919/2.0072.63110150215250
3×9511.45.50.825/0.851.919/2.0076.03460180260300
3×12012.85.50.825/0.852.019/2.0079.23810205300350
3×15014.25.51.025/0.852.019/2.0082.84230230340395
3×18515.75.51.025/0.852.119/2.0086.24650265390450
Heavy duty screen
3×356.95.50.840/0.851.87/2.0062.72510100140165
3×356.95.50.840/0.851.819/2.0066.72810105145165
3×508.15.50.823/1.351.819/2.0071.03300125175200
3×709.75.50.832/1.351.919/2.0074.63970155215250
3×9511.45.50.839/1.351.919/2.0078.04600180260305
3×12012.85.50.839/1.352.019/2.0081.24950205300350
3×15014.25.51.039/1.352.019/2.0084.85360230340395
3×18515.75.51.039/1.352.119/2.0088.25790265390450