MV ABC Wire SANS 1713

  • ABC Cable / Aerial Bundled CableTags: 33kV MV ABC Aluminium, MV ABC Wire

  • 2KM;

  • T/T, L/C, MoneyGram, Credit Card, Western Union, Cash;

  • Shipping fee and delivery date to be negotiated. Chat with supplier now for more details;

  • Every payment you make is secured with strict SSL encryption and PCI DSS data protection protocols;

  • FOB, CFR, EXW, FAS, DDP;

  • USD, EUR, CAD, AUD, GBP, CNY

Product Description

SANS 1713 Medium Voltage ABC cable range: 3.8/6.6kV, 6.35/11kV, 12.7/22kV , 19/33kV

MV ABC Wire Application

Suitable for aerial installation and for public power distribution networks

MV ABC Wire Standard

SANS 1713— Electric cables -Medium voltage aerial bundled conductors for voltages from 3,8/6,6 kV to 19/33 kV

MV ABC Wire Construction

Conductor types: Stranded hard drawn Aluminium class 2. Triple layer TR Cross linked polyethylene insulated, 3 cores, XLPE, individually screened, armoured and un-armoured cables in accordance with SANS 1713.

Size Range -Type A (Armoured) 95- 185 mm²(3.8/6,6kV, 6.35/11kV, 12.7/22kV,19/33kV)
Size Range -Type B (Unarmoure) 35 – 185 mm²(3.8/6,6kV, 6.35/11kV, 12.7/22kV)50- 185 mm2(19/33kV)

· 1.Conductor: Aluminum, circular stranded and compacted.

· 2.Conductor Screening: Extruded thermosetting semi-conductor layer.

· 3.Insulation: XLPE thermosetting material.

· 4.Insulation Screening: Semi conducting screen: Extruded thermosetting semi-conducting layer, applied under a swellable semi-conducting tape for water tightness.

· 5.Metal screen: Plain soft copper wire and / or copper tape applied helically, or aluminum tape applied longitudinally bonded to the outer PE sheath.

· 6.Outer sheath: Extruded black PE sheath, or PVC upon specific customer requirements.

· 7.Steel Messenger: 50 or 70 mm² galvanized steel stranded wires, covered with black PE, or PVC upon specific customer requirements.


6.6kV ABC Cable Specification
Phase Core
Conductor sizemm2 nom35507095120150185
Conductor diametermm app.7.158.259.9511.813.114.815.95
Insulation diametermm app.15.416.518.220.121.422.724.2
Core sheath diametermm app.20.521.623.525.526.828.129.9
Catenary (Support Core)
Conductor sizemm2 nom50505050707070
Conductor diametermm app.999910.810.810.8
Insulation diametermm app.11.511.511.511.513.313.313.3
Maximum tensile strength and pulling force of catenarykN26262626373737
Cable
Cable diametermm app.44475155586165
Cable masskg/m app.2.052.242.63.013.513.854.33
Gross mass (500m)kg app.9159731,0791,2041,3541,4541,599
Bending radiusmm min.636669720776841880926
Current rating
In airAmps150185230280325370430
Resistance
dc @ 20°CW/km max0.8680.6410.4430.320.2530.2060.164
ac @ 90°CW /km max1.1130.8220.5680.4110.3250.2650.211
ReactanceW /km0.1360.1240.1210.1140.1110.1060.103
ImpedanceW /km1.1210.8320.5810.4260.3420.2840.233
Short circuit ratings
SymmetricalkA (1 sec)345.8810.212.515.7
Earth faultkA (1 sec)1.51.61.71.922.12.3
         
11kv ABC Cable Specification
Phase Core
Conductor sizemm2 nom35507095120150185
Conductor diametermm app.7.158.259.9511.813.114.816.35
Insulation diametermm app.17.318.420.121.923.224.526.1
Core sheath diametermm app.22.523.625.327.428.730.231.7
Catenary (Support Core)
Conductor sizemm2 nom50505050707070
Conductor diametermm app.999910.810.810.8
Insulation diametermm app.11.511.511.511.513.313.313.3
Maximum tensile strength and pulling force of catenarykN26262626373737
Cable
Cable diametermm app.49515559626569
Cable masskg/m app.2.312.522.853.283.613.994.43
Gross mass (500m)kg app.9931,0551,1551,2851,3821,4961,628
Bending radiusmm min.691724775831896935981
Current rating
In airAmps150185230280325370430
Resistance
dc @ 20°CW/km max0.8680.6410.4430.320.2530.2060.164
ac @ 90°CW /km max1.1130.8220.5680.4110.3250.2650.211
ReactanceW /km0.1360.1240.1210.1140.1110.1060.103
ImpedanceW /km1.1210.8320.5810.4260.3420.2840.233
Short circuit ratings
SymmetricalkA (1 sec)345.8810.212.515.7
Earth faultkA (1 sec)1.51.61.71.922.12.3
         
22kV ABC Cable Specification
Phase Core
Conductor sizemm2 nom35507095120150185
Conductor diametermm app.7.158.259.9511.813.114.816.35
Insulation diametermm app.21.622.724.426.227.529.230.8
Core Sheath diametermm app.2728.13031.933.435.136.8
Catenary (Support Core)
Conductor sizemm2 nom50505050707070
Conductor diametermm app.999910.810.810.8
Insulation diametermm app.11.511.511.511.513.313.313.3
Maximum Tensile Strength and Pulling force of CatenarykN26262626373737
Cable
Cable diametermm app.58616569727680
Cable masskg/m app.2.963.193.614.054.635.065.61
Gross mass (500m)kg app.1 1881 2571 3831 5141 6901 8191 984
Bending radiusmm min.821854905960102510761123
Current rating
In airAmps150185230280325370430
Resistance
dc @ 20°CW/km max0.8680.6410.4430.320.2530.2060.164
ac @ 90°CW /km max1.1130.8220.5680.4110.3250.2650.211
ReactanceW /km0.1360.1240.1210.1140.1110.1060.103
ImpedanceW /km1.1210.8320.5810.4260.3420.2840.233
Short circuit ratings
SymmetricalkA (1sec)345.8810.212.515.7
Earth faultkA (1sec)1.51.61.71.922.12.3
         
33kV ABC Cable Specification
Phase Core
Conductor sizemm2 nom507095120150185 
Conductor diametermm app.8.259.9511.813.114.816.35 
Insulation diametermm app.27.829.531432.73435.5 
Core Sheath diametermm app.33.735.437.438.740.241.8 
Catenary (Support Core) 
Conductor sizemm2 nom505050707070 
Conductor diametermm app.99910.8|10.8010.8 
Insulation diametermm app.11.511.511.513.313.313.3 
Maximum Tensile Strength and Pulling force of CatenarykN262626373737 
Cable 
Cable diametermm app.737681848790 
Cable masskg/m app.4.124.535.065.375.826.33 
Gross mass (500m)kg app.1,5351,6581,8191,9102,0462,200 
Bending radiusmm min.1007105811141179|12181264 
Current rating 
In airAmps185230280325370430 
Resistance 
dc @ 20°CW/km max0.6410.4430.320.2530.2060.164 
ac @ 90°CW/km max0.8220.5680.4110.3250.2650.211 
ReactanceW /km0.1240.1210.1140.1110.1060.103 
ImpedanceW /km0.8320.5810.4260.3420.2840.233 
Short circuit ratings 
SymmetricalkA (1 sec)45.8810.212.515.7 
Earth faultkA (1 sec)1.61.71.922.12.3 